The General Electric Distribution Cable Terminal Block
is a modular attachment primarily used to provide an
alternate means of input to Spectra
®
RMS Molded-Case
Circuit Breakers with microEntelliGuard
TM
Trip Units. The
terminal block input/output connections are as follows:
Spectra
®
RMS Breaker with microEntelliGuard
TM
using
Terminal Block 11C
• Control power (+24vdc)
• Control power (-common)
• System communications (Comm. +)
• System communications (Comm. -)
• reduced energy let-through (RELT O +)
• ground fault alarm (GFA O +)
ground fault alarm/ reduced energy let-through
(RELT/GFA O –)
• reduced energy let-through (RELT I +)
• reduced energy let-through (RELT I –)
Neutral current sensor - black (for equipment ground
fault)
1
Neutral current sensor - white (for equipment ground
fault)
1
Spectra
®
RMS Breaker with microEntelliGuard
TM
using
Terminal Block 22C
• Control power (+24vdc)
• Control power (-common)
• System communications (Comm. +)
• System communications (Comm. -)
• reduced energy let-through (RELT O +)
• ground fault alarm (GFA O +)
ground fault alarm/ reduced energy let-through
(RELT/GFA O –)
• reduced energy let-through (RELT I +)
• reduced energy let-through (RELT I –)
Neutral current sensor - black (for equipment ground
fault)
1
Neutral current sensor - white (for equipment ground
fault)
1
• zone select interlock (ZSI I +)
• zone select interlock (ZSI I –)
• zone select interlock (ZSI O +)
• zone select interlock (ZSI O –)
• breaker position (Aux. Switch [RED] )
• breaker position (Aux. Switch [WHITE] )
voltage A (must be from Voltage Module or Voltage
Conditioner Plate or Voltage Conditioner Assembly)
voltage B (must be from Voltage Module or Voltage
Conditioner Plate or Voltage Conditioner Assembly)
voltage C (must be from Voltage Module or Voltage
Conditioner Plate or Voltage Conditioner Assembly)
GEH-706 Installation Instructions
Distribution Cable
Terminal Block
For Spectra
®
RMS Molded-Case Circuit Breakers
with microEntelliGuard
TM
Trip Units
For Catalog Number SDCTBA11C, SDCTBA22C
Circuit Breaker Accessory
GE Energy
Industrial Solutions
1
Neutral current sensor input is required for 3Ø /4W or 1Ø /3W systems. For 3Ø /3W systems, do not make any connections.
Page view 0
1 2 3 4 5 6 7 8

Summary of Contents

Page 1 - Terminal Block

OverviewThe General Electric Distribution Cable Terminal Block is a modular attachment primarily used to provide an alternate means of input to Spectr

Page 2

The Distribution Cable Terminal Block is used to carry a variety of electronic signals between Spectra® RMS Molded Case Circuit Breakers with microEnt

Page 3

GEH-706 Installation InstructionsFigure 2. Typical microEntelliGuardTM system utilizing the 22C Distribution Cable Terminal Block.Figure 3 shows the i

Page 4

GEH-706 Installation InstructionsDimensions and Wiring DiagramsA Distribution Cable Terminal Block dimensioned drawing is provided in Figures 4 &

Page 5

GEH-706 Installation InstructionsFigure 6 shows a point-to-point wiring diagram for a Distribution Cable Terminal Block SDCTBA11C connected to a Spect

Page 6

GEH-706 Installation InstructionsFigure 7. Wiring connections to the Distribution Cable Terminal Block 22C.

Page 7

GEH-706 Installation InstructionsConnectionsThe screw terminals on the Distribution Cable Terminal Block are labeled by function for clarity. The term

Page 8 - GEH-706 Rev. 3 (10/12 M45)

GEH-706 Rev. 3 (10/12 M45)imagination at workThese instructions do not cover all details or variations in equipment nor do they provide for every poss