Function
EntelliGuard TU Trip Units are designed with UL-Listed
interchangeable rating plugs. These rating plugs
change the per-unit (1X) continuous current rating of
the breaker. A circuit breaker frame equipped with a
suitable rating plug has a long-time trip value equal
to the ampere rating marked on the rating plug. For
example, a breaker frame with a 1600 A sensor and
an 800 A rating plug has an 800 A continuous current
(long-time) rating.
The available rating plugs for the AKR , Power Break,
WavePro and EntelliGuard families are listed in Table 1.
Not all sensors listed in Table 2 are available in all circuit
breakers.
Table 1. Rating plug catalog numbers
GTP0060U0101 GTP1100U1225
GTP0080U0101 GTP1200U1232
GTP0100U0103 GTP1500U1640
GTP0125U0103 GTP1600U1640
GTP0150U0104 GTP1900U2050
GTP0200U0204 GTP2000U2050
GTP0225U0306 GTP2200U2550
GTP0250U0407 GTP2400U2564
GTP0300U0408 GTP2500U2564
GTP0350U0408 GTP3000U3064
GTP0400U0410 GTP3200U3264
GTP0450U0612 GTP3600U4064
GTP0500U0613 GTP4000U4064
GTP0600U0616 GTP5000U5064
GTP0700U0816 GTP6000U6064
GTP0750U0820 GTP1600K4040*
GTP0800U0820 GTP2000K4040*
GTP0900U1020 GTP3000K4040*
GTP1000U1025 GTP4000K4040*
* For use with ITE 4000A conversion kits ONLY
Front Label
Figure 1. Front of rating plug, showing label
The front label, shown in Figure 1, is visible when the
rating plug is installed. The items listed are:
Rating Plug Amps (X) The rating plug continuous
current in amperes
Catalog Number GTP1100U1225
In this example:
GTP = EntelliGuard TU trip unit rating plug
1100 = The rating plug continuous current in amperes
U = Universal Trip Plug (Use K for ITE 400A sensor
conversion kit)
12 = Smallest sensor that accepts this plug (1200A)
25 = Largest sensor that accepts this plug (2500A)
Table 2. Catalog number sensor rating designations
Sensor Designation Sensor Rating
01 150A
02 200A
03 225A
04 400A
06 600A
07 630A
08 800A
10 1000A
12 1200A
13 1250A
16 1600A
20 2000A
25 2500A
30 3000A
32 3200A
40 4000A
50 5000A
60 6000A
64 6400A