Ge-industrial-solutions Record Plus FG600 SMR2 Modbus User Manual Page 13

  • Download
  • Add to my manuals
  • Print
  • Page
    / 21
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 12
SMR2 Modbus User Manual
10
Normal
mode - RO
3002 Seconds 0 - 59
Test mode
RW
Unsigned int
(Unused)
3003 Long Time Pickup 0-15 Normal
Mode--RO
_________
Test Mode
RW
Unsigned int
0 0.625
1 0.65
2 0.675
3 0.7
4 0.725
5 0.75
6 0.775
7 0.8
8 0.825
9 0.85
10 0.875
11 0.9
12 0.925
13 0.95
14 0.975
15 1.0
3004 Long Time delay 0-6 Normal
Mode--RO
_________
Test Mode
RW
Unsigned int
0 Line 1.25
1. Line 2.5
2. Line 5
3. Line 10
4. Motor 20
5. Motor 30
6.
3005
Short time pickup 0-9 Normal
Mode--RO
----------------------
Test Mode
RW
Unsigned int
3006 Short Time delay 0-9 Normal
Mode--RO
_________
Test Mode
RW
Value second I
2
T
0 40ms No
1 120ms No
2 210ms No
3 310ms No
4 420ms No
5 420ms Yes
6 310ms Yes
7 210ms Yes
8 120ms Yes
9 40ms Yes
3007 Ground Fault pickup 0-8 (in GF
module
0-9 (in GFA
module)
Normal
Mode--RO
_________
Test Mode
RW
Unsigned int
0 0.2X
1 0.3X
2 0.4X
3 0.5X
4 0.6X
5 0.7X
6 0.8X
7 0.9X
8 1.0X
Page view 12
1 2 ... 8 9 10 11 12 13 14 15 16 17 18 19 20 21

Comments to this Manuals