SMR2 Modbus User Manual
13
3029 Flag Cleared Byte 00 &
0xFF
Normal
mode - RO
00 Cleared (trip history can
not be shown on Flag
Module LEDs)
0xFFFF
Not Cleared (trip history can
be shown on Flag Module
LEDs)
3030 Test Kit Modbus Address 0 - 255 Normal
mode - RO
This is to test COMM
switches.
This returns the cumulative
Modbus address set through
two COMM switches.
3031 Test Kit Baud Rate 0 - 3 Normal
mode – RO
00 – 2400
01 – 4800
02 – 9600
03 – 19200
This is to test DIP switches.
3032 Ammeter Display Current 0 - 9999 Test mode
RW
Normal
mode - RO
This holds the value which is
displayed on LCD display
Value greater than 9999 will
be displayed as “----“
Test mode
RW
3033
Ammeter Display Current
Pushbutton
0 - 9999
Normal
mode - RO
Alternate value, which can be
written while testing
Ammeter module. As long as
Select_Phase is pushed, this
value gets displayed.
Value greater than 9999 will
be displayed as “----“
Event Registers
The trip unit stores up to eight events, with each event
utilizing 8 registers to describe the details of the event.
Last eight events are stored in chronological order, with
EVENT 1 being the oldest event and EVENT n being
the newest. An event is automatically cleared once read
by the host.