Ge-industrial-solutions Record Plus FG600 SMR2 Modbus User Manual Page 15

  • Download
  • Add to my manuals
  • Print
  • Page
    / 21
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 14
SMR2 Modbus User Manual
12
Test mode
RW
Normal
mode – RO
3019 Rating Plug Date Code
high
0-9999
Test mode
RW
Normal
mode - RO
3020 Rating Plug Date Code low 0-9999
Test mode
RW
Normal
mode - RO
3021 Rating Plug LT Settings 0 - 255
Test mode
RW
Normal
mode RO
3022 Number of Data bits 0-1
Test mode
RW
0 7-bits
1 8-bits
Normal
mode – RO
3023 Number of Stop bits 0-1
Test mode
RW
0 1-stop bit
1 2-stop bits
Normal
mode - RO
3024 Parity 0-2
Test mode
RW
0 No parity
1 Even Parity
2 Odd Parity
Normal
mode - RO
3025 Baud Rate 0- 3
Test mode
RW
0 2400
1 4800
2 9600
3 19200
3026 Modbus Address 1-247 Normal
mode - RO
ETU is known by this slave
address in the communication
network and communicates over
this address.
3027 LM1 Pickup 0-9
Normal mode
- RO
0 0.55
1 0.6
2 0.65
3 0.7
4 0.75
5 0.8
6 0.85
7 0.9
8 0.95
9 1.0
3028 LM2 Pickup 0-9
Normal mode
- RO
0 0.55
1. 0.6
2. 0.65
3. 0.7
4. 0.75
5. 0.8
6. 0.85
7. 0.9
8. 0.95
9. 1.0
Page view 14
1 2 ... 10 11 12 13 14 15 16 17 18 19 20 21

Comments to this Manuals