Ge-industrial-solutions Record Plus FG600 SMR2 Modbus User Manual Page 17

  • Download
  • Add to my manuals
  • Print
  • Page
    / 21
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 16
SMR2 Modbus User Manual
Reg Contents Units/
Range
Type
R/W
Format
2000 Event Code – Event 1 0-256 RO Unsigned int
2001 Hour 0 RO Unsigned int
2002 Minute 0 RO Unsigned int
2003 Second 0 RO Unsigned int
2004 Milliseconds 0 RO Unsigned int
2005 Event specific data 1 0 - 65535 RO Unsigned int
2006 Event specific data 2 0 - 65535 RO Unsigned int
2007 Event specific data 3 0 - 65535 RO Unsigned int
2008 Event code – Event 2 0-256 RO Unsigned int
2009 Hour 0 RO Unsigned int
2010 Minute 0 RO Unsigned int
2011 Second 0 RO Unsigned int
14
If another event occurs before the master reads all the
existing events, the oldest event is lost, new event data
will be placed in the EVENT 8 register, and the older
event register contents are shifted. The total number of
events since the last reset will be kept counted at
register location 1000-1001. Events are read using
Function Code 04.
2012 Milliseconds 0 RO Unsigned int
2013 Event specific data 1 0 - 65535 RO Unsigned int
2014 Event specific data 2 0 - 65535 RO Unsigned int
2015 Event specific data 3 0 - 65535 RO Unsigned int
… …
2056 Event code – Event 8 0-256 RO Unsigned int
2057 Hour 0 RO Unsigned int
2058 Minute 0 RO Unsigned int
2059 Second 0 RO Unsigned int
2060 Milliseconds 0 RO Unsigned int
2061 Event specific data 1 0 - 65535 RO Unsigned int
2062 Event specific data 2 0 - 65535 RO Unsigned int
2063 Event specific data 3 0 - 65535 RO Unsigned int