SMR2 Modbus User Manual
4
64h
03h
0Bh
C2h
00h
03h
CRCl
CRCh
Response: (register contents: 3010 = 022Bh, 3010 = 0000h,
3012 = 0066h)
Data
(n bytes)
Slave
Addres
s
(1byte)
Functio
n Code
(1 byte)
Numbe
r of
Bytes
(1byte)
Byte1
Byte2
-------
Byte n
CRC
(2
bytes
)
64h
03h
06h
02h 2Bh 00h
00h 00h 66h
CRCl
CRC
h
Read Input Registers (Function Code 04)
Use this command to read dynamic value or event
registers. Read the registers 1058 – 1060 from device
100:
Query:
Data
(n bytes)
Slave
Address
(1 byte)
Function
Code
(1 byte)
Start
Address
(2 bytes)
No. Of
Registers
(2 bytes)
CRC
(2 bytes)
64h
04h
04h 22h
00h 03h
CRCl
CRCh
Response: (register content: 1058 = FFFFh, 1059 = A01Ah,
1060 11B1h)
Data
(n bytes)
Slave
Addres
s
(1
byte)
Function
Code
(1 byte)
Number
of Bytes
(1 byte)
Byte1
Byte2
-------
Byte n
CRC
(2
bytes)
64h
04h
06h
FFh FFh A0h
1Ah 11h B1h
CRCl
CRCh
Force Single Coil (Function Code 05)
Use this command to perform remote control. This
command sets a single coil to enter ON or OFF.
Force coil 4 of device 100 ON (FF00h force on, 0000h
force off)
Query:
Data
(n bytes)
Slave
Address
(1 byte)
Function
Code
(1 byte)
Coil
Address
(2 bytes)
Data
(2
bytes)
CRC
(2 bytes)
64h
05h
00h 04h
FFh 00h
CRCl
CRCh
Response: (echo query message)
Data
(n bytes)
Slave
Address
(1 byte)
Function
Code
(1 byte)
Coil
Address
(2 bytes)
Data
(2
bytes)
CRC
(2 bytes)
64h
05h
00h 04h
FFh 00h
CRCl
CRCh
Preset Single Register (Function Code 06)
Use this command to write to a register. This presets a
value into a single holding register.
Preset register 0002 to 00 03 hex in slave device 17.
Query:
Data
(n bytes)
Slave
Address
(1 byte)
Function
Code
(1 byte)
Register
A
ddress
(2 bytes)
No. of
Registers
(2 bytes)
CRC
(2 bytes)
11h
06h
00h 02h
00h 03h
CRCl
CRCh
Response (echo query message)
Data
(n bytes)
Slave
Address
(1 byte)
Function
Code
(1 byte)
Register
ddress
(2 bytes)
No. of
Registers
(2
bytes)
CRC
(2 bytes)
11h
06h
00h 02h
00h 03h
CRCl
CRCh
Retransmit Last Message (Function Code 56)
Query:
Slave Address
(1 byte)
Function Code
(1 byte)
CRC
(2 bytes)
64h
38h
CRCl CRCh
Response
Slave
Function
Data
(n bytes)
CRC
Page view 6