SMR2 Modbus User Manual
Page view 0
1 2 3 4 5 6 ... 20 21

Summary of Contents

Page 1 - SMR2 Modbus User Manual

DEH41181 Rev01 g SMR2 Modbus User Manual

Page 2

SMR2 Modbus User Manual 7 Test mode -- RW 5 150/160 6 250/250 7 400/400 8 600/630 9 800/800 10 1200/1250 11 1600/1600 12 350 13 500 0007 Infor

Page 3 - Table of Contents

SMR2 Modbus User Manual 8 LT Accumulators (A, B, C & N) give normalized values and are typically max 1.25. Hence, they are multiplied with 10,000

Page 4 - Introduction

SMR2 Modbus User Manual Interpretation of SOS values The Sum Of Squares values (SOS) of a phase is a measure of the RMS value of current flowing thr

Page 5 - Electrical Interface

SMR2 Modbus User Manual 10Normal mode - RO 3002 Seconds 0 - 59 Test mode RW Unsigned int (Unused) 3003 Long Time Pickup 0-15 Normal Mode--RO ___

Page 6 - Modbus Message Frames

SMR2 Modbus User Manual 119 GFA Reset (In GFA module only) 3008 Ground Fault delay 0-9 Normal Mode RO _________ Test Mode RW Value second

Page 7

SMR2 Modbus User Manual 12 Test mode RW Normal mode – RO 3019 Rating Plug Date Code high 0-9999 Test mode RW Normal mode - RO 3020 Rating P

Page 8

SMR2 Modbus User Manual 13 3029 Flag Cleared Byte 00 & 0xFF Normal mode - RO 00 Cleared (trip history can not be shown on Flag Module LEDs)

Page 9 - Register Map

SMR2 Modbus User Manual Reg Contents Units/ Range Type R/W Format 2000 Event Code – Event 1 0-256 RO Unsigned int 2001 Hour 0 R

Page 10

SMR2 Modbus User Manual 15 Interpretation of Event Codes The following table describes the meaning of each event code Event Code (Hex) Mea

Page 11

SMR2 Modbus User Manual 16 Bit position in Bit map Bit Position in Bitmap Meaning Event code (Hex) 0 0 No Remote Trip 1 Remote Trip 6 1

Page 14

SMR2 Modbus User Manual g GE Consumer & Industrial General Electric Company 41 Woodford Ave., Plainvill

Page 15

SMR2 Modbus User Manual i Table of Contents Introduction ...

Page 16

SMR2 Modbus User Manual 2 Introduction The SMR2 trip unit has an optional communications module that facilitates monitoring of the trip unit via a ma

Page 17

SMR2 Modbus User Manual MODBUS ADDRESSES The master device addresses a specific slave device by placing the 8-bit slave address in the address fie

Page 18

SMR2 Modbus User Manual Figure2. Connection between Breaker and FAMECM module 3 Communication Environment • The trip unit is always the sla

Page 19

SMR2 Modbus User Manual 464h 03h 0Bh C2h 00h 03h CRCl CRCh Response: (register contents: 3010 = 022Bh, 3010 = 0000h, 3012 = 0066h) Data (n bytes)

Page 20

SMR2 Modbus User Manual 5Address (1 byte) Code (1 byte) Previous transmitted data (2 bytes) 64h 38h xxh xxh xxh xxh xxh xxh xxh xxh xxh CRCl CRCh

Page 21

SMR2 Modbus User Manual 2 Register Map While modbus communication with Target Communication Accessory module, all the registers are read only re